0

Out of 0 Ratings

Owner's of the APC Portable Generator APC Smart-UPS VA Tower gave it a score of 0 out of 5. Here's how the scores stacked up:
  • Reliability

    0 out of 5
  • Durability

    0 out of 5
  • Maintenance

    0 out of 5
  • Performance

    0 out of 5
  • Ease of Use

    0 out of 5
of 21
 
Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower 10
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in
the factory. These settings can only be modified using an external interface, like the NMC web interface.
NMC IP Address Mode
NMC IP Address
NMC Subnet Mask
NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in
seconds
The amount of time the UPS or Switched Outlet
Group will wait between receiving the command
to turn on and the actual startup.
Turn Off Delay 0 sec Set the value in
seconds
The amount of time that the UPS or Switched
Outlet Group will wait between receiving the
command to turn off and the actual shut down.
Reboot Duration 4 sec Set the value in
seconds
The amount of time that the UPS or Switched
Outlet Group must remain off before it will
restart.
Minimum Return
Time
0 sec Set the value in
seconds
The amount of battery runtime that must be
available before the UPS or Switched Outlet
Group will turn on.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS
can disconnect power to the Switched Outlet
Group to save runtime.
Configure this delay time, use the
LOAD SHED
T
IME WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime
Disabled • Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the battery runtime falls below the
specified value, the Switched Outlet Group will
turn off.
Configure this time using the
LOAD SHED
R
UNTIME REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level,
the Switched Outlet Group will turn off.
Load Shed on
Overload
Disabled • Disabled
•Enabled
In the event of an overload (greater than 100%
output), the Switched Outlet Group will
immediately turn off to conserve power for
critical loads. The Switched Outlet Group will
only turn on again with a manual command.