Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower 8
Low Transfer
Point
120 V:
106 Vac
• 97 Vac
• 100 Vac
• 103 Vac
• 106 Vac
Set the transfer point lower if the utility
voltage is chronically low and the connected
equipment can tolerate this condition.This
setting may also be adjusted using the power
quality setting.
Note: Use the Advanced Menus to configure
this setting.
230 V:
208 Vac
• 196 Vac
• 200 Vac
• 204 Vac
• 208 Vac
Nominal Output
Voltage
120 Vac N/A Set the nominal output voltage of the UPS on
battery. This is available on 230 V models
only.
230 Vac 208-252 Vac
Transfer
Sensitivity
High High, Low, Medium Select the level of sensitivity to power events
that the UPS will tolerate.
• High: The UPS will go on battery power
more often to provide the cleanest power
supply to the connected equipment.
• Low: The UPS will tolerate more
fluctuations in power and will go on battery
power less often.
If the connected load is sensitive to power
disturbances, set the sensitivity to High.
Low Battery
Warning
120 sec Set the value in
seconds
The UPS will emit an audible alarm when the
remaining runtime has reached this level.
Date of Last
Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off The UPS will mute all audible alarms if this is
set to Off or when the display buttons are
pressed.
Battery Self-
Test Interval
Setting
On start-up and
every 14 days since
the last test
• Never
• Start-up only
• Frequency of test
(days)
The interval at which the UPS will execute a
self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description